Product Core Brief
- Model: CC-PDIS01
- Brand: HONEYWELL
- Series: Experion C300
- Core Function: Acquires 32 digital inputs with Sequence of Events recording capability.
- Product Type: Digital Input Module
- Key Specs: 32 Channels | SOE Function | 24 VDC
- Condition: New Original (New Surplus)
Product Introduction
HONEYWELL CC- serves as a 32-channel digital input module for C300 controllers. It captures discrete signals while providing precise Sequence of Events (SOE) timestamping for fault analysis.
This module supports 24 VDC signals with configurable filter times down to 5 ms in fast mode. Integrated open-circuit detection helps identify field wiring issues immediately. Verify with OEM datasheet for exact SOE resolution, though 1 ms is the typical field standard.

CC-PDOB01
Key Technical Specifications
| Parameter | Value |
|---|---|
| Channel Count | 32 Inputs |
| Signal Type | Digital (Dry Contact / Source / Sink) |
| Nominal Voltage | 24 VDC |
| SOE Resolution | 1 ms |
| Filter Time | 5 ms (Fast) / 20 ms (Normal) |
| Isolation | 1500 VAC (Channel-to-System) |
| Field Power Output | 24 VDC @ 0.7 A |
| Hot Swap | Supported |
| Series Compatibility | Experion C300 |
| Diagnostic Coverage | Open Circuit Detection |
Quality Control Process (Engineer’s Perspective)
- Incoming Verification: We trace source documentation and verify serial numbers against anti-counterfeit databases. Visual inspection checks for PCB corrosion or connector scratches.
- Live Functional Test: Power-on self-tests run first. We verify communication handshakes and execute continuous load runs exceeding 24 hours with temperature logging.
- Electrical Parameter Test: Insulation resistance gets measured at 500 V using a Megger. Readings must exceed 10 MΩ. Ground continuity is also confirmed.
- Firmware Verification: We read and record the firmware version. DIP switch and jumper settings receive photographic documentation before shipping.
- Final QC & Packaging: The unit seals in an anti-static bag. A QC Passed label with the test date goes on the exterior.

CC-PDOB01
Replacement Pitfall Guide
❗ Firmware Mismatch: New hardware often ships with newer firmware. This causes bus errors if the controller expects an older revision. Always match the existing system version.
❗ DIP Switch / Jumper Misconfiguration: Factory defaults rarely match your field settings. Check the bus termination resistor position on the third terminal block. Wrong settings kill communication.
❗ Terminal / Cable Incompatibility: Pin definitions change between revisions. Verify shield grounding at the cabinet entry point. Floating shields introduce noise into safety channels.
❗ Power Supply Mismatch: Calculate total rack power consumption carefully. Add 20% headroom for inrush currents. Undersized supplies cause intermittent module resets during startup.
❗ ESD Damage: Use a grounded anti-static mat during installation. Dry environments increase static risk significantly. One spark destroys internal logic gates.
Keep these in mind and you’ll cut 90% of rework time.
Compatibility Matrix & Benchmarks
- HONEYWELL CC- → HONEYWELL CC- : Direct — Identical replacement
- HONEYWELL CC- → HONEYWELL CC-PDIL01 : Needs Adaptation — CC-PDIL01 lacks SOE function, verify timing requirements
- HONEYWELL CC- → HONEYWELL CC-TDIL01 : Incompatible — CC-TDIL01 is a terminal base, not an active module
- HONEYWELL CC- → HONEYWELL CC-PDOB01 : Incompatible — Digital output vs digital input
- SOE Timestamp: < 1 ms (Resolution verified)
- Bus Handshake: < 500 ms (Cold start to operational)