Product Core Brief
- Brand: GE Fanuc / Emerson Automation
- Model: IC695PSA140
- Series: PACSystems RX3i
- Core Function: 40W universal multi-purpose backplane power supply accepting wide-range AC or DC mains input; supplies regulated multi-rail logic power to RX3i universal backplane plus auxiliary 24VDC relay output, supports load sharing and N+1 redundant parallel operation for high availability control racks
- Type: Two-slot rack-mounted backplane power supply
- Condition: New Original (New Surplus)
- Status: ⚠️ Discontinued OEM active production; limited surplus inventory
- Key Spec Highlights: 85–264VAC / 100–300VDC wide universal input, total 40W rated output, +5.1V / +3.3V backplane rails + auxiliary 24VDC, load-sharing redundancy capable, four front diagnostic LEDs, occupies two consecutive RX3i backplane slots
Key Technical Specifications
- Nominal Input: 120/240 VAC or 125 VDC AC range: 85–264 VAC, 47–63 Hz DC range: 100–300 VDC
- Maximum Input Power: 70 W
- Total Rated Output Power: 40 W maximum (thermal derating above 40°C)
- Output Rails · +5.1 VDC (max 30 W) · +3.3 VDC (max 30 W) · Auxiliary +24 VDC for external relay loads
- Backplane Occupancy: Requires two consecutive universal backplane slots
- Maximum Units Per Chassis: Up to four modules for load sharing and redundant architectures
- Front Panel Indicators: POWER, P/S FAULT, OVER TEMP, OVERLOAD LEDs
- Front Control: Protected output on/off switch (does not disconnect incoming mains power)
- Protections: Overload, overvoltage, short-circuit, over-temperature shutdown
- Input-to-Backplane Isolation: 1500 VAC for 1 minute
- Hot Swap: Not supported; system power should be isolated before module removal
- Operating Temperature: 0 °C to +60 °C
- Storage Temperature: −40 °C to +85 °C
- Humidity: 5%–95% non‑condensing
- Wiring Terminals: Accepts 14 AWG – 22 AWG copper conductors
- Certifications: UL, CE, ATEX, DNVGL marine approval
- Variant Suffixes: IC695PSA140CA (conformal coated), IC695PSA140LT (low temperature version)
- Compatible Hardware: Full IC695 RX3i CPU, communications and I/O modules; universal backplane only
Product Introduction
Critical power, chemical and water treatment facilities often require PLC racks to connect directly to industrial AC mains or high-voltage DC station batteries. GE is a universal-input power supply designed to eliminate separate transformers or DC converters by accepting either standard AC utility power or 125 VDC battery supply.
This unit supports parallel load-sharing redundant configurations to remove single points of power failure. The auxiliary 24VDC output powers field relays without extra cabinet power supplies. As a two-slot module, space planning must account for double slot occupancy during rack layout or spare replacement.
Key Selling Points & Differentiators
- GE supports universal AC and high-voltage DC input, ideal for power plant and marine installations with mixed mains / battery power infrastructure.
- Native load-sharing circuitry enables N+1 redundant power architectures for continuous-process control systems.
- Every unit undergoes full bench validation on an RX3i test chassis; variable load testing, fault diagnostics and rail stability verified prior to shipment. Signed test documentation available on formal request. Warranty runs 12 months post delivery.
- Independent auxiliary 24VDC relay output reduces cabinet component count and wiring complexity.
- Not recommended for RX7i, Series 90‑70 or Series 90‑30 racks. Designed exclusively for RX3i universal backplane architecture.
- Clear four-channel LED diagnostics allow operators to rapidly isolate overload, thermal and supply fault conditions without dedicated diagnostic software.
Quality Transparency SOP
- Incoming Verification: Serial traceability validation, anti-counterfeit visual inspection, terminal block and switch hardware integrity cross-check.
- Live Bench Test: Dedicated RX3i test rack, power-on self-test, AC/DC input range sweep, multi-rail variable load simulation, fault alarm verification, continuous 24-hour thermal soak cycling.
- Electrical Tests: Insulation resistance testing via 500 V megger, chassis ground continuity validation.
- Hardware Verification: Confirm LED array and output switch operate per datasheet; no unauthorized component rework performed.
- Final QC & Packaging: Anti-static shielding, shock-dampened transit carton, signed QC Pass label. Test images and logs available on request. No zero-failure performance guarantee.
Technical Risk Avoidance Section
Slot Occupancy Risk Risk: Designers treat it as single-slot module; insufficient free slots lead to rack layout errors. Prevention: Reserve two consecutive empty slots for installation. Field note: Multiple retrofit projects failed to install replacement units after reserving only one slot position.
Thermal Derating Risk Risk: Operating continuously above 40°C requires reduced total rack load; full 40W capacity cannot be sustained. Prevention: Calculate total backplane power consumption and apply temperature-based derating rules for enclosed cabinets.
Hot Swap Risk Risk: Inserting/removing module with mains energized creates arcing and may damage backplane contacts. Prevention: Isolate upstream AC/DC power before module replacement.
Input Confusion Risk Risk: Confusing (AC/DC high voltage input, two slots) with IC695PSD140E (24VDC input, single slot) leads to wrong spare ordering. Prevention: Confirm site incoming power type and slot space before procurement.
Critical Summary: Confirm incoming power type and available rack slots before procurement. This universal AC/DC power supply occupies two slots and cannot be directly substituted with 24VDC input PSD series power supplies without cabinet power redesign.