Product Core Brief
- Model:
- Brand: GE Fanuc / Emerson Automation
- Series: Series 90-30 PLC
- Core Function: 16-point positive logic (Sourcing / Source) DC discrete output module. Converts %Q discrete signals into DC output to drive solenoid valves, solid-state relays, indicator lights and DC loads.
- Product Type: Single-width Series90-30 DC Discrete Output Module
- Key Specs: 16 sourcing outputs | 4 groups × 4 channels | 2A per channel continuous | 12/24VDC field supply | Group-to-group galvanic isolation | Non-isolated backplane to field Note: Discontinued legacy Series90-30 I/O module; new original stock scarce, surplus & refurbished widely available. Does NOT support hot swap. Install directly on IC693CHS Series90-30 backplanes. Cannot plug into IC694 or IC695 RX3i racks. Conformal coated variant: IC693MDL730CA.
Key Technical Specifications
- Channel Layout: 16 sourcing DC outputs, divided into 4 independent common groups (4 channels per group)
- Wiring Logic: Positive Logic (Sourcing) – module provides positive DC potential to field loads
- Field Operating Voltage Range: 10 ~ 30 VDC (nominal 12 / 24 VDC)
- Output Ratings Per channel continuous current: 2 A Per common group maximum: 4 A Module total maximum: 16 A Minimum load current: 10 mA Max inrush current: 5 A (10ms)
- Electrical Characteristics Maximum voltage drop: ≤1.0 VDC at rated load Off-state leakage current: ≤1 mA Response Time: Max 2 ms turn-on / 2 ms turn-off
- Isolation Rating: 500 VAC group-to-group isolation; 1500 VAC field-to-backplane isolation
- Backplane Power Consumption 5 VDC: 110 mA (all outputs ON)
- Front Panel Indicators: 16 independent channel status LEDs
- Internal Protection: No channel fuses; external field fusing recommended
- Operating Temperature: 0°C ~ +60°C horizontal cabinet mounting
- Storage Temperature: -40°C ~ +85°C
- Form Factor: Single-width module for Series90-30 backplane
- Compatible Baseplates: IC693CHS391 (5-slot), IC693CHS392 (10-slot)
- Supported Software: Logicmaster 90, Proficy Machine Edition
- Agency Certifications: UL508, Class I Div.2, CE
Product Introduction
is a high-current sourcing DC discrete output module for Series 90-30 PLC, widely used in machine automation, packaging and hydraulic/pneumatic valve control.
Important Module Family Distinction
- : 16-point, 2A per channel sourcing output (high current DC)
- IC693MDL740: 16-point, 0.5A per channel sourcing output (lower power)
- IC693MDL940: Relay dry contact output module
- IC694MDL730: Equivalent module for IC694 serial expansion racks (form factor incompatible)
Four independent common groups allow different DC potentials on separate groups, improving wiring flexibility. Group isolation suppresses cross-group noise interference.
Critical Wiring Note: Sourcing (source) output matches sinking (NPN) field loads. For sinking PLC outputs (sink type), select MDL750 series.
This module is not HART-capable, only for discrete on/off DC loads.
QA & Testing SOP (Transparency Building)
- Incoming Inspection: Verify part marking. Inspect backplane gold pins for oxidation/bending; check module housing integrity.
- Live Testing: Mount onto validated Series90-30 backplane. Apply rack power and external 24VDC field supply. Toggle each channel, verify output voltage under resistive load, check LED status, run continuous 24-hour switching stability test.
- Electrical Testing: Monitor backplane 5V rail stability. Insulation resistance ≥10MΩ between field terminals and chassis protective ground.
- Documentation: Photograph terminal wiring layout before disassembly; record hardware revision.
- Final QC & Packaging: Place unit inside anti-static shielding. Attach dated QC test tag confirming channel switching validation prior to shipment.
Installation Pitfalls & Guide
❗ No Hot Swap Support: Series90-30 I/O modules cannot be hot swapped. Full rack power shutdown mandatory before removal. ❗ External DC Field Supply Mandate: Output drive power comes from external field 12/24VDC; backplane power only for module logic. ❗ Current Budget Control: Do not exceed 2A per channel / 4A per common group rating; overload accelerates internal power device degradation. ❗ Sourcing Load Matching: Designed for NPN sinking loads; incorrect wiring will prevent load actuation. ❗ External Fusing Recommendation: No built-in channel fuses; add branch fuses for short-circuit protection. ❗ Conformal Coated Variant: IC693MDL730CA for humid/corrosive environments; electrically identical. ❗ Inductive Load Protection: Install flyback diodes across solenoid coils to absorb inductive kickback. ❗ ESD Risk: Static discharge damages output power semiconductors leading to channel dropout or permanent failure.
Replacement Guide
- Pre-install: Lockout-tagout rack power; back up PLC I/O configuration. Photograph slot arrangement and field wiring mapping.
- Removal: Disconnect all field output wiring, unlatch module and slide straight out without twisting backplane pins.
- Install: Seat new into original slot, replicate all field wiring connections.
- Power-on Test: Restore rack power; confirm all channel LED operation, verify main CPU can toggle all %Q discrete outputs normally.
FAQ
Q: Does support hot swapping? A: No. Series90-30 I/O modules do not support hot swap. Full rack power shutdown required.
Q: What is the difference between and IC693MDL740? A:
- : 2A per channel high-current sourcing output
- IC693MDL740: 0.5A per channel standard sourcing output Pinout and form factor identical; check load current before interchange.
Q: Can I install directly into RX3i main IC695CHS007 rack? A: No. Native Series90-30 module. RX3i usage requires remote serial expansion rack with IC695LRE001.
Q: What is sourcing (positive logic) output? A: Module supplies positive DC voltage to the load; load return connects to DC negative (GND). Suitable for NPN field sensors and solenoids.
Q: Can different voltage potentials be used on separate groups? A: Yes, each group is isolated; maintain consistent voltage within one common group.
Q: Will saved I/O configuration automatically work after replacement? A: Discrete channel configuration resides in the PLC project. After replacement, verify all output points can be toggled normally.