Product Core Brief
- Model:
- Brand: GE Fanuc / GE
- Series: Series 90-30 PLC
- Core Function: Delivers regulated multi-rail power to Series 90-30 main and expansion backplanes; universal AC/DC wide-range input.
- Product Type: High Capacity Universal Input Power Supply Module
- Key Specs: 30W total output | 85–264VAC / 100–300VDC input | Three independent DC output rails Note: Discontinued legacy hardware; factory new stock scarce, surplus and refurbished units widely traded. Must occupy Slot 0 (far-left dedicated power slot). Hot swapping is not supported.
Key Technical Specifications
- Nominal Input: 120/240 VAC or 125 VDC
- Operating Input Range: 85–264 VAC (47–63 Hz); 100–300 VDC
- Total Rated Output Power: 30 W combined across all rails
- Output Rails: +5 VDC (up to 30 W maximum for backplane logic) +24 VDC Relay Power (15 W maximum) Isolated +24 VDC (20 W maximum)
- Minimum Hold-Up Time: 20 ms
- Isolation Rating: 1500 VAC input-to-backplane isolation, 1-minute withstand
- Protections: Overvoltage, overcurrent, auto-recovering short-circuit shutdown
- Status Indicators: Power OK LED, Fault LED, Battery status terminal
- Operating Temperature: 0°C to 55°C horizontal cabinet mounting
- Storage Temperature: -40°C to 85°C
- Form Factor: Single-width Series 90-30 slot
- Compatible Chassis: IC693CHS391, IC693CHS392, IC693CHS397, IC693CHS398
- Terminal Wire Range: 14 AWG to 22 AWG copper conductors
Product Introduction
This unit supplies stable multi-domain power for Series 90-30 racks designed for mains AC or high-voltage DC plant power. It distributes logic power to the backplane and provides separate 24V supplies for relay outputs and discrete field I/O modules.
Flexible power allocation allows the full 30W capacity to be allocated to the +5VDC rail for racks with high CPU and I/O density. The universal input eliminates jumper adjustments for global mains voltage variants, common for overseas machine exports and plant retrofits.
QA & Testing SOP (Transparency Building)
- Incoming Inspection: Verify part marking and hardware revision suffix. Inspect edge connector pins for bending or corrosion; check terminal block housing for cracks.
- Live Testing: Mount to validated Series 90-30 backplane, apply nominal AC input. Load all output rails and monitor voltage stability through a continuous 24-hour run cycle.
- Electrical Testing: Use Fluke 115 to track rail regulation. Insulation resistance testing must exceed 10MΩ between input terminals and chassis protective ground.
- Documentation Check: Record hardware revision. Photograph input wiring layout before disassembly.
- Final QC & Packaging: Place unit inside anti-static shielding. Attach dated QC test tag listing steady-state voltage readings prior to shipment.
Installation Pitfalls & Guide (Engineer to Engineer)
❗ No Hot Swap Support: Series 90-30 backplanes lack hot-swap bus logic. Live removal crashes all rack modules and risks permanent backplane trace damage. Full rack power shutdown mandatory. ❗ Slot Placement Mandate: Install only in the far-left dedicated power slot (Slot 0). Insertion into regular I/O slots prevents backplane power distribution and will not operate. ❗ Input Type Confusion: This universal AC/DC input module cannot be directly swapped with IC693PWR331 (24VDC input). Mismatched input power will destroy the power supply. ❗ ESD Dangers: Exposed backplane connector circuits are static-sensitive. Un-grounded handling can create drifting output regulation that appears after commissioning. ❗ Power Budget Miscalculation: Sum total power draw of all installed modules. Overloading the 30W total rating creates voltage sag, random CPU faults and intermittent module dropouts.
Replacement Guide:
- Pre-install: Activate lockout-tagout on rack input power; document all input wiring connections.
- Removal: Disconnect AC/DC input terminals, unlatch module and slide straight out without twisting edge connectors.
- Install: Seat new unit fully into Slot 0, lock latches, terminate input wiring and verify torque on terminal screws.
- Power-on Test: Restore input power, confirm Power OK LED illuminates; power up CPU and verify all I/O modules are recognized by programming software.
FAQ (Frequently Asked Questions)
Q: Does this unit support hot swapping? A: No. The Series 90-30 backplane architecture does not support live power supply removal. Full rack power shutdown is required for replacement.
Q: What is the difference between and IC693PWR331? A: accepts universal 85–264VAC / 100–300VDC input. IC693PWR331 is designed for 24VDC nominal input. They are not direct interchangeable. Confirm site power source before replacement.
Q: Can this power supply be used inside RX3i racks? A: No. Form factor, pinout and signaling are exclusive to Series 90-30 chassis. It cannot operate within PACSystem RX3i hardware.
Q: Can multiple power supplies run in parallel for redundancy? A: Load sharing and redundant parallel operation are not supported. Each rack requires one dedicated power supply. Deploy separate racks for fault-tolerant layouts.
Q: What happens during a short-circuit on any output rail? A: The supply triggers auto-recovering current limiting. Persistent faults will assert the Fault LED and halt output regulation until input power is cycled.
Q: Can I use this unit on Series 90-30 remote expansion racks? A: Yes, it is compatible for expansion baseplates, provided the rack is configured to accept this universal input power supply. Confirm rack power budget before loading I/O modules.
Q: Will a replacement unit work without configuration changes? A: No software configuration is required for power supplies. After installation, verify all rail voltages and monitor for intermittent fault codes caused by overloaded backplane loads.