Product Core Brief
- Model: IC200ALG326H
- Brand: GE (General Electric) / GE Fanuc
- Series: VersaMax PLC
- Core Function: Provides eight 4-20mA analog current-sourcing outputs to drive control valves, actuators, and other field devices.
- Product Type: Analog Output Module (AO)
- Key Specs: 8 Channels | 13-Bit Resolution | 4-20mA Current Sourcing | Part Number
- Condition: New Original (New Surplus) | Factory Sealed
Key Technical Specifications
| Parameter | Value |
|---|---|
| Module Type | Analog Output Module (Current Sourcing) |
| System Platform | GE VersaMax PLC |
| Channel Count | 8 Independent Output Channels |
| Resolution | 13-Bit |
| Output Signal Type | 4-20mA (Configurable to 0-20mA via Jumper) |
| Overrange Capability | Up to ~20.38mA per channel |
| Power Requirement | External Field-Side DC Power Required |
| Status Indicators | Green FLD PWR LED, Green OK LED |
| Backplane Power | +5VDC @ 50mA per output |
| Environmental Rating | Industrial Grade |
| Condition | New Original (New Surplus) |
| Warranty | 1-Year Functional Warranty |

GE IC200ALG331
Product Introduction
Delivering precise analog control to field devices requires a reliable and high-resolution interface, and the is engineered to provide exactly that. Functioning as an 8-channel analog output module, this card provides 13-bit current-sourcing outputs, making it ideal for driving multiple control valves, VFD speed references, or process actuators from a single VersaMax PLC slot.
Designed for industrial environments, the requires an external field-side DC power supply to drive the output loads. It features dual LED indicators for immediate visual troubleshooting: a green “OK” LED confirms backplane power, while the “FLD PWR” LED confirms the presence of external field power. Its flexible jumper configuration allows technicians to tailor output behavior during power loss or communication interruptions.
Key Selling Points & Differentiators
- High-Density 8-Channel Output: Maximizes I/O density by providing eight independent 4-20mA outputs in a single VersaMax module slot.
- 13-Bit High Resolution: Delivers precise current control with a modest overrange capability (up to ~20.38mA) to ensure accurate actuator positioning.
- Flexible Loss-of-Signal Behavior: Jumper-selectable configuration allows outputs to either hold their last state or default to the low end of the range if backplane power or communications are interrupted.
- Verified Functionality: Every undergoes channel-by-channel current injection and load testing before shipping, complete with a signed test report.
- Not Recommended For: Do not use this module without an external field power supply, as it only sources current and does not generate field loop power.
- Stock Availability: Current inventory is factory-sealed new surplus with traceable lot numbers; typically ships within 48 hours of order confirmation.
- Warranty Backed: Includes a 1-year functional warranty covering manufacturing defects and DOA conditions, with no restocking fees for verified failures.

GE IC200ALG331
FAQ
Yes. All units in stock have passed our 8-channel output load tests. We ship same-day for orders placed before 2 PM EST, so you’ll have tracking before end of day.
Does this module provide loop power to my field devices?
No. The is a current-sourcing module. You must provide an external DC power supply (typically 18-30 VDC) to the field-side terminals to complete the 4-20mA loop and drive the loads.
How do I configure the output behavior during a PLC fault?
The module features a hardware jumper that dictates fail-safe behavior. You can configure the outputs to either hold their last commanded value or drop to the low end of the range (0mA/4mA) if the PLC stops or backplane communication is lost. Critical: Always configure jumpers with power OFF.
Do I need to reconfigure the module after installation?
The hardware configuration is jumper-based, but the engineering unit scaling and output limits must be set in your VersaPro or Machine Edition software. If replacing a failed module, verify the jumper settings match the old unit and download the program to restore scaling.
What if the module fails within the warranty period?
We offer a no-questions-asked replacement for any verified manufacturing defect. Ship the failed unit back with your RMA number, and we’ll send a replacement within 24 hours of receipt.
Is this a refurbished or new surplus unit?
This is New Original (New Surplus) – factory sealed, never installed, with full traceability to the original manufacturing lot. It is not refurbished, repaired, or pulled from a decommissioned system. We provide the original manufacturer’s lot code upon request for your quality records.
Quality Transparency SOP
- Incoming Verification: Source traceability confirmed via lot code; anti-counterfeit visual inspection; serial number cross-referenced with OEM records; jumper configuration verified.
- Live Bench Test: Dedicated VersaMax test rack; power-on self-check; 8-channel current sourcing validation; external field power loop test; 24-hour continuous load test; signed test report generated.
- Electrical Tests: Insulation resistance verified at 500V megger (>10 MΩ); ground continuity confirmed; backplane power consumption validated.
- Firmware Verification: N/A (Hardware-configured module).
- Final QC & Packaging: QC sign-off; anti-static seal applied; shock protection installed; QC Passed label affixed with date and inspector ID.
Test photos and video available upon request. We never claim “100% failure-free” – we provide verified, tested units with documented performance.
Technical Risk Avoidance
- Missing Field Power: Risk: Outputs remain at 0mA. Prevention: Verify the external field-side DC power supply is connected and the green “FLD PWR” LED is illuminated. Field Note: We’ve seen technicians replace a perfectly good module because they forgot to wire the external 24VDC field supply. Always check the FLD PWR LED.
- Jumper Misconfiguration: Risk: Valves fail open or fail closed unexpectedly during a fault. Prevention: Verify jumpers match your process safety requirements (Hold Last State vs. Default Low). Field Note: A valve defaulted to 0mA during a brief PLC reboot because the jumper was set incorrectly, causing a process trip. Always map jumpers.
- Backplane Seating: Risk: Intermittent output updates. Prevention: Ensure the module is fully seated and locked onto the VersaMax backplane. Field Note: A partially seated module caused random valve chatter during panel vibration. Push firmly until the latch clicks.
- Scaling Errors: Risk: Incorrect valve positioning. Prevention: Verify engineering unit scaling in the PLC program matches the field actuator. Field Note: A 4-20mA signal commanded 50% but drove the valve to 100% because the 13-bit raw count scaling wasn’t updated after replacement. Always verify scaling.
- ESD Damage: Risk: Silent channel failure. Prevention: Use grounded wrist strap and anti-static mat during handling. Field Note: We’ve tested modules that passed power-on but had dead output channels after 48 hours due to ESD. Handle with care.