Woodward 9905-068 | Digital Synchronizer & Load Control for Generator Systems

  • Model: 9905-068
  • Alt. P/N: 9905-068B, 9905-068C, 9905-068D (later revisions)
  • Series: Woodward Digital Synchronizers
  • Type: Microprocessor-based synchronizer & load control
  • Key Feature: Digital phase detection, automatic voltage matching, load sharing interface
  • Primary Use: Synchronizing generator to grid with integrated load/import-export control
In Stock
Manufacturer:
Part number: Woodward 9905-068
Our extensive catalogue, including : Woodward 9905-068 , is available now for dispatch to the worldwide. Brand:

Description

Key Technical Specifications
  • Model Number: 9905-068
  • Manufacturer: Woodward
  • Sensing Voltage: 115 VAC or 230 VAC (jumper-selectable), 45-65 Hz
  • Power Supply: 18-32 VDC or 88-132 VAC (selectable)
  • Power Consumption: 15 W max
  • Phase Window: ±0.5° electrical (digital calculation)
  • Slip Frequency: 0.02-0.5 Hz programmable
  • Speed Bias Output: 0-10 VDC or 4-20 mA into 500 Ω
  • Load Control Output: 4-20 mA for import/export or base load
  • Breaker Control: 2× Form-C relays, 5 A @ 250 VAC/30 VDC
  • Communications: RS-485 Modbus RTU (optional on base, standard on later revs)
  • Display: 4-digit LED for frequency, phase angle, voltage differential
  • Operating Temperature: –20 °C to +60 °C
  • Mounting: 8.5″ × 4″ panel-mount chassis, DIN rail optional

    WOODWARD 9905-068

    WOODWARD 9905-068

Field Application & Problem Solved
Old analog synchroscopes work until they don’t—drift, calibration issues, and human error cause more breaker trips than actual faults. The 9905-068 is Woodward’s digital upgrade: a microprocessor watches generator and bus waveforms, calculates phase angle within half a degree, and closes the breaker at the exact zero-crossing. I install these on 5-20 MW cogen units in refineries and paper mills where they parallel multiple times daily with the utility. The built-in load control means it doesn’t just sync—it manages import/export setpoints via 4-20 mA to the 2301A or 505, holding a dead-band of ±10 kW so the utility never sees a swing. One box replaces the synchroscope, the import/export card (9905-092), and the manual load trim pot. Commissioning: set PT ratio, dial in your dead-band, and let it run—no more operator guessing games.
Installation & Maintenance Pitfalls (Expert Tips)
Ground the Shield at One End Only—But Pick the Right End
The 9905-068 has enough digital noise immunity to survive most plants, but the PT cables are the weak link. I ground the shield at the card end, never at the switchgear—ground loops will give you ±2° phase jitter and the breaker will chatter instead of closing clean.
Program the Slip Frequency Before You Apply Generator Voltage
Default is 0.1 Hz, which is fine for 4-pole machines. On a 3600 RPM gas turbine, 0.1 Hz is too sloppy—you’ll see 10° phase error at closure. Drop it to 0.02 Hz in the menu, but realize the sync check takes 30 seconds longer. Balance speed against accuracy for your application.
Base Revision Has Limited Communications
The base 9905-068 has an RS-485 port, but early firmware only supported basic Modbus. If you need full SCADA integration, flash to revision C.2 or later, or upgrade to the 9905-068C. Check the firmware version on power-up—if it’s pre-2.0, you’re limited to polling frequency and phase angle only.
Don’t Trust the LED Display for Phase Angle
It’s accurate to ±0.5°, but only updates every 100 ms. If your slip is 0.3 Hz, the real phase angle has moved 10.8° between updates. Use the analog speed bias output to verify the loop is actually tracking—scope it for a clean ramp, not steps.
Check the Relay Contact Rating—It’s Not 10 A
The Form-C outputs are rated 5 A resistive, 2 A inductive. I’ve seen techs drive a 5 A breaker coil directly; the contacts weld in six months. Interpose a 24 VDC ice-cube relay, or better yet, use the dry contacts to pull in a PLC input and let the PLC handle the heavy lifting.

WOODWARD 9905-068

WOODWARD 9905-068

Technical Deep Dive & Overview
The 9905-068 is a 16-bit microprocessor-based synchronizer built around an Intel 80C196 microcontroller. Input transformers scale PT signals to 5 VAC; a 12-bit A/D samples both channels at 1 kHz, and firmware calculates zero-crossings, phase angle, and slip frequency using a 3-sample digital filter. The phase-locked loop updates every 10 ms, outputting a 0-10 VDC speed bias to the governor’s auxiliary input.
Load control runs on a separate PID loop: the 4-20 mA output biases the speed reference to hold import/export setpoints, with programmable dead-band and rate limiting. Two Form-C relays provide “SYNC OK” and “BREAKER CLOSE” signals; both are debounced in firmware to prevent chatter. The RS-485 port exposes frequency, voltage, phase angle, and relay status for SCADA integration—Modbus register map is in manual 26270.
The base revision uses through-hole construction for the power supply section and early-vintage electrolytic capacitors. It runs fine in clean environments, but for harsh sites with H₂S or high humidity, look for the 9905-068C with surface-mount components, upgraded capacitors, and better conformal coating. Boot time is 2 seconds; if the CPU doesn’t see valid PT signals within 5 seconds, it flags “SENSING FAULT” and opens the relays.