Description
Hard-Numbers: Technical Specifications
- Processor: 1.2 GHz AMD G-Series quad-core
- Memory: 4 GB DDR3-1333 SDRAM (ECC), 4 GB NAND flash
- NVSRAM: 3067 nonvolatile variables, 64 totalizers, 338 forces
- OS: QNX Neutrino RTOS (v6.5 / v7.1) with hypervisor
- Ethernet: 6× 10/100/1000 (5 front, 1 bottom dedicated Predix/EFA)
- Protocols: IONet, UDH, TCP/IP, Modbus TCP, OPC UA, Embedded EtherCAT, PPNG
- Redundancy: Simplex, Dual, TMR supported
- Power: 24 VDC (±10%), 28 W max
- Cooling: Passive convection (fanless)
- Temp: -40°C to +70°C (operating); -40°C to +85°C (storage)
- Dimensions: 168 × 150 × 55 mm (8.03 × 5.99 × 2.17 in)
- Weight: ~1.32 kg (2.91 lbs)
- Certifications: UL, CE, cULus, DNV, IEC 61000 (EMC)
- HMI: ControlST V07.00.00C or later

IS420UCSCH1A
The Real-World Problem It Solves
is the upgraded gateway variant of IS420UCSCH1A. It acts as a bridge between Mark VIe/VIeS safety systems (UCSB) and external networks/devices. It offloads non-safety communication (OPC UA, Modbus, cloud) to avoid loading safety controllers, while supporting advanced protocols like EtherCAT for modern fieldbus integration.
Typical Applications:
- Primary gateway between Mark VIeS safety and non-safety networks
- OPC UA / Modbus TCP server for SCADA/HMI connectivity
- Edge data acquisition with Predix EFA cloud integration
- Gas/steam turbine auxiliary systems control
- Compressor/pump control with third-party device integration
Hardware Architecture & Logic Flow
- Isolated Gateway Path: Separates safety (IONet) and non-safety (UDH/EtherCAT) networks
- Quad-Core Parallel Processing: Runs control logic, communication stacks, and diagnostics simultaneously
- Redundant Peer Sync: <1 ms skew for failover; supports TMR for high availability
- Dedicated Predix Port: Bottom RJ45 exclusively for EFA/cloud to avoid network contention
- Hardware Watchdog: Automatic fault recovery; non-safety only (no SIL rating)
Field Service Pitfalls (Rookie Mistakes)
1. Safety Function Misuse
- Critical: Not SIL rated. Never use for SIS/ESD logic (use UCSB series).
- Rule: = gateway/non-safety control only; safety functions → IS420UCSBS1A/BH4A.
2. Network Port Misconfiguration
- Bottom port is factory-locked for Predix/EFA. Reassigning breaks cloud connectivity.
- Fix: Use front 5 ports for control/I/O; reserve bottom for EFA only.
3. Inadequate Cooling Clearance
- Passive cooling requires airflow. Blocked heatsinks → thermal throttling & comms dropouts.
- Fix: Mount vertically; 50 mm clearance top/bottom; cabinet ventilation.
4. Firmware & Software Mismatch
- Requires ControlST V07.00.00C+; older versions fail to recognize EtherCAT/PPNG.
- Rule: Never load Safety ToolboxST firmware; use standard ControlST only.
IS420UCSCH1A
Commercial Note
Please note: The listed price is for reference only and is not binding. Final pricing and terms are subject to negotiation based on current market conditions and availability.