Description
Hard-Numbers: Technical Specifications
- Network: Dual 10/100Mbps IONet Ethernet (RJ45)
- Input Channels: 12× isolated thermocouple/mV inputs
- Supported Types: E, J, K, S, T (grounded/ungrounded)
- Input Span: -8 mV to +45 mV
- Resolution: 16-bit A/D converter
- Isolation: 2500V DC field-to-backplane
- Common Mode: ±5 V, 100dB rejection @50/60Hz
- Accuracy: ±0.25°F (±0.14°C) full scale
- Processor: AMD-K6 300 MHz
- Power: 24 VDC (22.5–28.6V), soft-start, 7.5W max
- Temp Range: -30°C to +65°C
- Dimensions: 82.6 × 41.9 × 121 mm
- Weight: ~0.9 kg
- Certifications: Class I Div 2, Zone 2 hazardous locations
- LEDs: PWR, ATTN, ACT1, ACT2, TEMP (diagnostic)

IS220PAICH1A
The Real-World Problem It Solves
Gas/steam turbines require precision temperature monitoring to prevent overheating, optimize efficiency, and extend component life. eliminates noise, drift, and ground-loop errors common in generic temperature I/O.Typical Applications:
- Turbine exhaust thermometry
- Compressor & bearing temperature monitoring
- Combustion chamber temperature profiling
- Steam generator & heat recovery systems
Bottom line: delivers lab-grade accuracy in harsh turbine environments with TMR-ready reliability.
Hardware Architecture & Under-the-Hood Logic
combines a common Mark VIe processor board with a dedicated thermocouple acquisition board:
- Thermocouple signals route to isolated signal conditioning circuits.
- Cold-junction compensation (CJC) sensors auto-calibrate for terminal temperature.
- 16-bit ADC digitizes inputs at >1000 samples/sec.
- On-board processor linearizes readings per thermocouple type.
- Dual IONet ports stream data to the main controller.
- Internal diagnostics detect open circuits, short circuits, and out-of-range values.
- Conformal coating protects against corrosion and vibration.

IS220PAICH1A
Field Service Pitfalls: What Rookies Get Wrong
Thermocouple Type Mismatch
- Issue: Wrong type selected in ToolboxST (e.g., J vs K) causes >50°C error.
- Fix: Match software type to physical thermocouple; label wires/couples.
Ground Loop Creation
- Issue: Thermocouple grounded at both ends induces noise; unstable readings.
- Fix: Use ungrounded couples; single-point ground at TBTCH terminal.
Excessive Cable Resistance
- Issue: Wire >450Ω resistance causes signal attenuation.
- Fix: Use 24AWG twisted-pair; limit cable length to <984ft (300m).
Over-Torqued Terminals
- Issue: Tightening >0.5 N·m cracks TBTCH blocks; intermittent opens.
- Fix: Torque to 0.5 N·m (4.4 lb·in); replace damaged blocks.
Commercial Availability & Pricing Note
Please note: The listed price is for reference only and is not binding. Final pricing and terms are subject to negotiation based on current market conditions and availability.