Description
Component Snapshot At-a-Glance
- Model: IS220PSCAH1B
- Alt. P/N: 336A4940CSP10
- Product Series: GE Speedtronic Mark VIe / VIeS
- Hardware Type: Serial Communication (PSCA) I/O Pack
- Key Feature: 6 isolated, software-configurable serial ports (RS-232/422/485)
- Primary Field Use: Connects Mark VIe IONet to Modbus RTU devices and legacy serial equipment

IS220PAICH1A
Hard-Numbers: Technical Specifications
- Protocol Support: Modbus RTU, IONet 100Mbps full-duplex Ethernet
- Port Count: 2× RJ45 Ethernet; 6× isolated serial (DC-62 field connector)
- Serial Standards: RS-232, RS-422, RS-485 half-duplex (per-channel config)
- Baud Rates: 300–115200 baud (software selectable)
- Isolation Rating: 2500 VAC RMS field-to-backplane
- Power Requirements: 24 VDC (22.5–28.6V), 8.5W max draw
- Operating Temperature: -30°C to +70°C
- Weight: 0.8 kg
- Dimensions: 8.26 × 4.19 × 15 cm
- Certifications: UL, CSA, CE; Class I Div 2, Zone 2
- Field Wiring: 24 AWG minimum
- Diagnostics: Internal watchdog, channel status LEDs
The Real-World Problem It Solves
Legacy serial devices lack direct Ethernet links to Mark VIe controllers. External gateways introduce latency, extra wiring, and single points of failure.
Where you’ll typically find it:
- Turbine control to Modbus flow meters and gas analyzers
- Power plant SCADA links to legacy PLCs and remote HMI terminals
- Refinery RS-485 sensor networks for pressure and level transmitters
Bottom line: integrates serial assets directly into Mark VIe without external gateways.
Hardware Architecture & Under-the-Hood Logic
uses a common Mark VIe processor board with a dedicated serial transceiver board. Isolation barriers separate field signals from backplane electronics.
- Serial signals terminate at the DC-62 field connector.
- Each channel passes through 2500V isolation to block ground loops.
- On-board MCU handles Modbus RTU framing and error checking.
- Dual RJ45 ports provide redundant IONet connectivity.
- Local processor converts serial data to IONet packets.
- Channel status LEDs and internal diagnostics monitor health.
- Watchdog timer resets the module on communication faults.

IS220PAICH1A
Field Service Pitfalls: What Rookies Get Wrong
RS-485 Termination & Bias NeglectRookies skip 120Ω termination or bias resistors. Bus floats; data garbles or drops out intermittently.
- Field Rule: Terminate only at bus endpoints. Add 1kΩ pull-up/pull-down bias on the master port.
Excessive RS-232 Cable LengthUsing RS-232 over 15 meters causes signal degradation. Data errors and timeouts occur.
- Quick Fix: Use RS-422/485 for runs >15m. Keep RS-232 cables short and fully shielded.
Mixed Ground PotentialsConnecting remote devices with mismatched grounds destroys non-isolated transceivers.
- Field Rule: Use isolated ports for cross-cabinet runs. Never tie field grounds to cabinet backplane.
Commercial Availability & Pricing Note
Please note: The listed price is for reference only and is not binding. Final pricing and terms are subject to negotiation based on current market conditions and availability.