Description
Hard-Numbers: Technical Specifications
- Protocol Support: IONet (Mark VIe proprietary), 100Mbps Ethernet
- Port Count: 2× RJ45 Ethernet, 1× DC-37 field I/O connector
- Input Channels: 24 discrete, dry contact/24V DC compatible
- Input Voltage: 18–32 VDC (nominal 24 VDC)
- Isolation Rating: 2500 VAC optical (input-to-backplane/channel-to-channel)
- Input Filter: 2 ms configurable hardware debounce
- Power Draw: 3.0 W typical; 28.0 VDC nominal input
- Operating Temperature: -30°C to +65°C
- Storage Temperature: -40°C to +70°C
- Dimensions: 226 × 107 × 30 mm (W×H×D)
- Weight: 0.8 kg
- Hazardous Rating: Class I Div 2, Zone 2, ATEX / IECEx approved

IS220PDIOH1B
The Real-World Problem It Solves
Critical turbine systems face ground loops and EMI-induced false trips from unisolated discrete signals. Unfiltered contact bounce causes unstable logic and unplanned downtime in power generation.
Where you’ll typically find it:
- Gas turbine ignition and starter permissive interlocks
- Steam turbine emergency trip (ETS) limit switch monitoring
- Compressor anti-surge valve position feedback loops
Bottom line: eliminates signal cross-talk and stabilizes discrete inputs in high-noise industrial environments.
Hardware Architecture & Under-the-Hood Logic
integrates a 32-bit RISC processor and high-voltage opto-isolation. It operates autonomously for I/O scanning, reducing main controller overhead.
- Field signals terminate at the DC-37 connector.
- Signals pass through 2500V optical isolation barriers.
- On-board filtering suppresses transient noise (2ms fixed).
- Local microprocessor scans and validates channel states.
- Data transmits over dual redundant Ethernet to the Mark VIe controller.
- Per-channel diagnostics detect open circuits and over-voltage conditions.
- Front-panel LEDs indicate power, fault, and Ethernet link status.
Field Service Pitfalls: What Rookies Get Wrong
Under-Voltage OperationTechnicians often apply 24.0 VDC and report intermittent input dropouts. Minimum reliable voltage is 27.4 VDC under full load.
- Field Rule: Set supply to 28.0 VDC. Verify at module terminals with all channels active.
Shield Ground LoopsRookies ground field cable shields at both ends. Induced currents create false input triggers.
- Quick Fix: Terminate shield only at the marshalling cabinet; float the module end.
Hot-Swap DamageReplacing under power causes backplane glitches that lock the I/O node.
- Field Rule: De-energize the rack or disable node via Toolbox. Wait 30 seconds before swapping.