GE DS3800NPSE1D1F | Power-Supply Sequencer Board for Mark IV Turbine & EX2000 Exciters

  • Brand: General Electric
  • Model: DS3800NPSE1D1F
  • Product Type: Power-Supply Sequencer / Field & Gate Power Board
  • Series: DS3800, Mark IV / EX2000 Speedtronic
  • Core Function: Sequences and regulates +24 Vdc field bus and ±15 Vdc gate-drive rails; clamps surges and reports power-good status to the CPU.
  • Key Specs: 6BA Euro-card format, epoxy-sealed non-repairable construction, 24 Vdc @ 3 A field output, ±15 V gate drive, 0–60 °C operating range.
In Stock
Manufacturer:
Part number: DS3800NPSE1D1F
Our extensive catalogue, including : DS3800NPSE1D1F , is available now for dispatch to the worldwide.

Description

DS3800NPSE1D1F Product Overview
The DS3800NPSE1D1F is a power-supply sequencer board used inside GE Mark IV turbine and EX2000 exciter control racks. It occupies a 6BA Euro-card slot and performs three essential functions:
  1. Field Power Sequencing – It converts raw 120–240 VAC control-transformer power into a regulated +24 Vdc field bus (3 A) for contactor coils and auxiliary relays, bringing the rail up in a defined order to prevent the SCR bridge from firing into an un-powered CPU.
  2. Gate-Drive Generation – It boosts 5 V logic fire pulses from the CPU to ±15 V isolated gate signals and delivers them to the six-pulse bridge via fiber-optic ST ports.
  3. Surge Clamping & Status – On-board 40 mm MOVs absorb lightning or switching transients, while opto-isolated “POWER GOOD” lines report under-voltage or MOV-fail conditions to the CPU.
All copper traces are fully encapsulated in high-temperature epoxy, making the unit non-repairable—any internal fault requires a complete card swap rather than component-level rework. The module is fully hot-swappable when the rack is powered down, and its 1.5 lb weight allows adjacent-slot population without additional support brackets.

GE DS3800NDID1P1H

GE DS3800NDID1P1H

DS3800NPSE1D1F Technical Specifications
  • Model Number: DS3800NPSE1D1F
  • Manufacturer: General Electric
  • Product Type: Power-Supply Sequencer / Field & Gate Power Board
  • Series: DS3800, Mark IV / EX2000 Speedtronic
  • Form Factor: 6BA Euro-card (≈ 233 × 160 mm)
  • Back-Plane Connector: Dual 40-pin header (J1/J2)
  • Field Power Output: +24 Vdc @ 3 A (current-limited)
  • Gate Drive Output: ±15 Vdc isolated, 2 A peak per bridge leg
  • Surge Protection: 40 mm MOVs, 1 kJ pulse rating

  • Isolation: 1500 Vdc input-to-logic; 2.5 kV optical on gate fibers
  • Operating Temperature: 0 – 60 °C
  • Weight: ≈ 1.5 lb (≈ 0.68 kg)
  • Construction: Epoxy-sealed copper traces—non-repairable

    GE DS3800NDID1P1H

    GE DS3800NDID1P1H

Core Features & Customer Value
Integrated Power & Gate Drive: By combining 24 V field supply and ±15 V gate drive on one card, the module eliminates separate power supplies and gate amplifiers. For the maintenance crew this means fewer spare part numbers to stock and a single five-minute swap instead of troubleshooting three separate boards.
Epoxy-Sealed Construction: All internal copper is encapsulated in high-temperature epoxy. In environments with high humidity, dust, or conductive contamination the seal prevents trace-to-trace shorting that would otherwise cause random “FIELD POWER FAIL” alarms after ten-plus years of service. The trade-off is non-repairability—any internal fault requires a whole-card exchange—but this is offset by the reduced diagnostic time and the fact that plants stock one spare instead of maintaining a repair bench.
Wide AC Input Window: The board accepts 120–240 VAC directly from the control transformer. This allows the same part number to be used on 120 V or 240 V services without additional taps or selectors, simplifying spares inventory and reducing wiring errors during retrofit projects.
Typical Applications
In combined-cycle power plants the board is installed in the Mark IV exciter cubicle where it provides the gate-drive interface for the six-pulse SCR bridge. During a black-start the card ramps the 24 V contactor bus and the ±15 V gate supply in sequence, preventing the bridge from firing into an un-powered CPU

.

On mechanical-drive gas compressors the same module is used to fire the variable-speed drive IGBT stack. The on-board MOV string clamps lightning-induced surges on the 480 VAC feeder, while the scaled ±10 V feedback signals allow the CPU to compute firing angle without additional signal-conditioning hardware. Because the card is line-replaceable, a surge event that damages any internal layer is corrected with a five-minute swap rather than a half-shift re-cabling job.