The DS200TCQBG1BCA is an RST Extended Analog I/O printed-circuit board used inside GE Mark V Speedtronic turbine and compressor control cubicles. It occupies a standard card slot on the Mark V control backplane and acts as the low-level interface between the controller’s analog-to-digital converters and field 4–20 mA or 0–200 mA loops.
The card is part of the DS200 “RST” family of Mark V personality boards—modules that share the same 96-pin edge connector and mechanical envelope but implement dedicated analog or timing functions. Using a common hardware platform allows plant stores to stock one spare chassis and populate it with the exact personality boards required for each turbine section.

IS200WETAH1ADC
-
Model Number: DS200TCQBG1BCA
-
Manufacturer: General Electric
-
Product Type: RST Extended Analog I/O Board
-
Input Channels: 15 differential, milliampere (4–20 mA default)
-
Output Channels: 2 milliampere, jumper-selectable 20 mA or 200 mA full-scale
-
Burden Resistor: 250 Ω ±0.1 % (inputs)
-
Output Compliance: 20 V @ 200 mA (max)
-
Jumper Banks: BJ1-BJ17 (BJ1-BJ15 = input range / DCOM; BJ16-BJ17 = output range select)
-
Isolation: Basic insulation; field-side common tied to DCOM jumper
-
Memory: On-board EPROM for calibration constants
-
Status Indication: Front-panel green “OK” LED
-
Connectors: 96-pin DIN edge finger (backplane), no external field terminals
-
Mounting: Standard Mark V card rails, captive screws
-
Weight: ≈ 0.25 kg (0.55 lb)
-
Operating Temperature: 0 … +55 °C (Mark V cabinet ambient)
-
Storage Temperature: –40 … +85 °C
-
Vibration/Shock: 5 g / 50 g (per Mark V cabinet spec)
15 + 2 channel density – One card replaces separate input and output analog boards, freeing Mark V slots and reducing spare-part count while keeping the same 4–20 mA / 0–200 mA capability.
Drop-in spare – Shares the DS200 RST form factor with earlier TCQ* revisions; no mounting changes, no parameter downloads, and no calibration required during swap-out.

IS200WETAH1ADC
In combined-cycle plants the DS200TCQBG1BCA is installed in the “analog I/O” section of Mark V panels that govern gas-turbine fuel flow, inlet-guide-vane position, and cooling-water temperature. The 15 input channels accept 4–20 mA from pressure and temperature transmitters, while the two 200 mA outputs drive magnetic amplifiers or servo-valve coils.