Description
Key Technical Specifications
-
Model Number: INICT01
-
Manufacturer: ABB Bailey
-
Protocol Support: INFI-Net serial, RS-232-C ASCII
-
Ports: 1× RS-232-C DB-9 (DCE), 1× INFI-Net backplane
-
Data Rate: 50 – 19 200 baud (DIP selectable)
-
Memory: 256 kB ROM, 512 kB RAM, 80 kB NVRAM
-
Power: +5 VDC 4.2 A, +15 VDC 40 mA, −15 VDC 20 mA (back-plate)
-
Isolation: 1500 V logic-to-network
-
Operating Temperature: 0 °C to +70 °C
-
Dimensions: single-width INFI 90 module, 70 × 37 × 20 mm
-
Weight: 120 g
-
RoHS: Exempt per 2011/65/EU
ABB INICT01
Field Application & Problem Solved
In the field, the biggest pain is getting an old INFI-90 rack to talk to a modern PC. INICT01 is the serial bridge—plugs into the backplane, spits out RS-232 at 19.2 k, and lets your HMI/SCADA pull live data without a $2 000 gateway box. You’ll typically find it bolted to the side of turbine panels, flare skids, or any 90-series rack where an engineer still wants to use Wonderware or a custom VB app. Its main value: it off-loads the CPU from bit-banging serial and gives you a standard DB-9 you can cable directly to a COM port or USB-serial dongle.
In the field, the biggest pain is getting an old INFI-90 rack to talk to a modern PC. INICT01 is the serial bridge—plugs into the backplane, spits out RS-232 at 19.2 k, and lets your HMI/SCADA pull live data without a $2 000 gateway box. You’ll typically find it bolted to the side of turbine panels, flare skids, or any 90-series rack where an engineer still wants to use Wonderware or a custom VB app. Its main value: it off-loads the CPU from bit-banging serial and gives you a standard DB-9 you can cable directly to a COM port or USB-serial dongle.
Installation & Maintenance Pitfalls (Expert Tips)
Baud DIP switches lie – Set them before you insert the card. If you change them live, the module won’t switch until the next rack power-cycle.
DB-9 pin-out trap – Pin 2 TX, Pin 3 RX, Pin 5 GND. If your PC cable is null-modem, you’ll swap TX/RX and get silence—meter the cable first.
Backplane power dip – Card runs on +5 V 4 A. If your rack supply sags below 4.8 V, the module resets and you’ll see garbage on the terminal. Check +5 V under load.
NVRAM battery – No battery, but if you lose +5 V you lose the baud-rate DIP setting. Write it on a label taped to the card.
Termination resistor – RS-232 doesn’t need one, but if you run RS-485 out of a converter, terminate 120 Ω at the far end or you’ll chase ghosts.

ABB INICT01
Technical Deep Dive & Overview
INICT01 is a passive serial gateway—no CPU onboard. It grabs a 512-byte buffer from INFI-Net every 100 ms and shoves it out the DB-9 at the selected baud. Inside is a 68000-family UART, 256 kB ROM for firmware, and 80 kB NVRAM for buffer scratch. The card keys itself into the backplane; don’t force it or you’ll break the plastic lock. Lose +5 V and the whole card goes dark—tie it to the same UPS feeding the CPU.
INICT01 is a passive serial gateway—no CPU onboard. It grabs a 512-byte buffer from INFI-Net every 100 ms and shoves it out the DB-9 at the selected baud. Inside is a 68000-family UART, 256 kB ROM for firmware, and 80 kB NVRAM for buffer scratch. The card keys itself into the backplane; don’t force it or you’ll break the plastic lock. Lose +5 V and the whole card goes dark—tie it to the same UPS feeding the CPU.