Product Core Brief
- Model: 330980-51-00
- Brand: BENTLY NEVADA
- Series: 3300 XL 8mm
- Core Function: Conditions eddy current probe signals into buffered voltage and current outputs.
- Product Type: Proximitors (Signal Conditioner)
- Key Specs: -24Vdc Nominal | 100mV/mil Sensitivity | 8mm System
- Condition: New Original / New Surplus
Product Introduction
BENTLY 330980-51-00 is a 3300 XL 8mm proximitors for industrial vibration monitoring. It accepts raw probe signals and delivers buffered -Vout and 4-20mA outputs to your monitoring system.
This industrial automation unit operates from -17.5Vdc to -26Vdc with excellent RF immunity. It supports both DIN rail and panel mounting without external isolation plates.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Input Power | -24Vdc Nominal (-17.5 to -26Vdc) |
| Power Consumption | Max 12mA |
| Sensitivity | 100 mV/mil (3.94 V/mm) |
| Output Signal | Buffered -Vout & 4-20mA |
| Frequency Response | 0–10 kHz (-3dB) |
| Linearity Error | < 1% Full Scale |
| Operating Temp | -40°C to +85°C |
| Mounting Options | DIN Rail / Panel |
| RF Immunity | CE Compliant (No Shielding Needed) |
| System Compatibility | 3300 XL 8mm Probes |
Quality Control Process
We validate every BENTLY 330980-51-00 before it ships. First, we verify power supply rejection using a programmable DC source. Output must remain stable across the full -17.5Vdc to -26Vdc range.
Next, we inject a calibrated RF signal to test immunity. The 330980-51-00 must reject interference without output spikes. We also verify 4-20mA loop accuracy with a precision process calibrator.
Finally, each replacement module ships in anti-static shielding with desiccant. This prevents moisture damage during transit.

BENTLY 330980-51-00
Replacement Pitfall Guide
❗ Sensitivity Mismatch: The “-51” code dictates 100mV/mil sensitivity. Installing a 200mV/mil proximitors with an 8mm probe will double your vibration readings and cause false trips.
❗ Power Polarity: This unit requires negative DC power. Reversing polarity destroys the internal FETs instantly. Double-check your power supply wiring before energizing.
❗ Grounding Strategy: The mounting base is electrically isolated. Do not assume chassis ground. Connect the shield drain wire to the proximitors ground terminal only.
❗ Cable Length Limits: Total system length (probe + extension) must match the proximitors calibration. Swapping a 5m system for a 9m system without recalibration ruins linearity.
Keep these in mind and you’ll cut 90% of rework time.
Compatibility Matrix & Benchmarks
| Original Model | Replacement / Successor Model | Compatibility Level | Migration Notes |
|---|---|---|---|
| 330980-51-00 | 330980-50-00 | Direct | Verify sensitivity matches |
| 330980-51-00 | 330980-70-00 | Needs Adaptation | Different output configuration |
| 330980-51-00 | 330180-51-00 | Direct | Older 3300 series; check specs |
- Output Drive: 500Ω max loop impedance
- Response Time: < 1ms for 4-20mA output