Product Core Brief
- Model: 330104-00-07-10-12-00
- Brand: Bently Nevada
- Series: 3300 XL 8mm
- Core Function: Non-contact shaft vibration and position measurement.
- Product Type: Proximity Probe Transducer
- Key Specs: 7.87 V/mm | 100°C Rating | 2mm Linear Range
- Condition: New Original / New Surplus

330104-00-06-10-02-00
Product Introduction
The Bently 330104-00-07-10-12-00 provides precise eddy current displacement sensing. This proximity probe monitors critical rotating machinery health.
This industrial automation unit delivers 7.87 V/mm sensitivity reliably. It maintains linearity across a 2mm measurement range without drift.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Tip Diameter | 8 mm (0.315 in) |
| Sensitivity | 7.87 V/mm (200 mV/mil) |
| Linear Range | 2 mm (80 mils) |
| Frequency Response | 0 to 10,000 Hz |
| Max Temp Rating | 100°C (212°F) |
| Thread Size | M10 x 1.0 |
| Cable Length | 1.0 m (3.3 ft) |
| Supply Voltage | -24 VDC Nominal |
| Output Type | Analog Voltage |
| Compliance | API 670 |
Quality Control Process
Every replacement module undergoes rigorous electrical validation. We measure coil resistance with a Fluke multimeter first. Values must match the calibration certificate exactly. Next, we verify sensitivity using a precision micrometer stage. Linearity deviation beyond ±2% triggers immediate rejection. We then perform thermal soak testing at 100°C. This confirms insulation integrity under load. Finally, we inspect connector pins for oxidation. All units ship in anti-static shielding.
Replacement Pitfall Guide
❗ Check the Temp Code. The “10” in this model means 100°C max. Installing this in a 150°C zone destroys the coil insulation rapidly. Verify your operating environment first.
❗ Match Cable Length Exactly. This 1.0m cable length is electrically critical. Substituting a 2m version changes system capacitance. Your gap voltage will drift without recalibration.
❗ Avoid Ground Loops. Never ground the shield at both probe and monitor. Ground loops inject 60Hz hum into your vibration signal. Isolate the shield at the chassis only.
❗ Set Gap Voltage Correctly. Target -10.0 VDC ± 0.2V for this sensitivity. A 0.5V offset causes >10% amplitude error. Do not eyeball this setting.
Keep these in mind and you’ll cut 90% of rework time.

330104-00-06-10-02-00
Compatibility Matrix & Benchmarks
| Original Model | Replacement / Successor Model | Compatibility Level | Migration Notes |
|---|---|---|---|
| 330104-00-07-10-12-00 | 330104-00-07-10-12-00 | Direct | Identical electrical specs |
| 330104-00-07-10-12-00 | 330104-00-07-50-12-00 | Needs Adaptation | 185°C rating changes coil specs |
| 330104-00-07-10-12-00 | 330104-00-07-10-02-00 | Needs Adaptation | 2m cable requires recalibration |
- Dynamic Range: >60 dB typical signal-to-noise ratio.
- Response Time: <10 µs step response for transient capture.