Product Core Brief
- Model:
- Brand: GE Fanuc / Emerson Automation
- Series: PACSystems RX3i
- Core Function: High-density universal analog input module, converts analog voltage/current field signals into digital %AI register values for the RX3i CPU. Supports flexible wiring mode selection: 16 single-ended channels or 8 differential channels.
- Product Type: Single-width RX3i Non-Isolated Analog Input Module
- Key Specs: 24-bit Sigma-Delta ADC | Software-selectable signal ranges | Configurable digital low-pass filters | Supports hot swap on certified RX3i backplanes Note: Active lifecycle RX3i analog module; new original, surplus & refurbished stock available. -EA = PCB hardware revision suffix, mechanically interchangeable with other variants. Non-isolated design (common analog ground); not channel-to-channel isolated. Terminal block IC694TBB032 (screw) / IC694TBS032 (spring) sold separately. No native HART support.
Key Technical Specifications
- Channel Configuration (software selectable, whole module uniform mode): 16 single-ended inputs OR 8 differential input pairs
- Supported Signal Ranges (per-channel independent configuration): Voltage: ±10 V, 0–10 V, ±5 V, 0–5 V, 1–5 V Current: 4–20 mA, 0–20 mA, ±20 mA
- ADC Resolution: 24-bit Sigma-Delta conversion
- Data Format: Selectable 32-bit floating-point or 16-bit integer
- Configurable Low-Pass Filter Cutoff: 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 500 Hz
- Input Impedance Voltage inputs: >100 kΩ Current inputs: Internal precision 249 Ω shunt
- Diagnostics: Open-circuit detection, over-range / under-range alarm, rate-of-change fault monitoring
- Backplane Power Consumption 3.3 VDC: 375 mA 5 VDC: 180 mA
- Isolation: Backplane-to-field isolation only; NO channel-to-channel galvanic isolation
- Overvoltage Protection: ±60 VDC continuous input withstand
- Status LEDs: MODULE OK, FIELD STATUS
- Operating Temperature: 0°C ~ +60°C horizontal cabinet mounting
- Storage Temperature: -40°C ~ +85°C
- Form Factor: Single-width RX3i module
- Compatible Baseplates: IC695CHS007, IC695CHS012, IC695CHS016 universal RX3i racks
- Required Terminal Block: IC694TBB032 (captive screw) or IC694TBS032 (spring clamp)
- Supported Software: Proficy Machine Edition
- Agency Certifications: UL508, Class I Div.2, CE
Product Introduction
is a high-density universal analog input module for PACSystems RX3i, widely used for monitoring pressure, flow, level, temperature transmitters and analog transducers. Engineers select wiring topology via PME software: single-ended for high channel count, differential wiring to suppress common-mode noise in noisy industrial environments. Multiple digital filter options allow balancing signal smoothness and response speed without external analog filters.
Critical Selection Distinction
- : Non-isolated, high channel density, cost-effective for systems with unified field ground.
- IC695ALG626: Channel-group isolated version of 16-channel AI for applications prone to ground loops. This module does not support HART protocol. For HART-capable analog inputs select dedicated HART AI modules.
Important wiring note: Non-isolated architecture means all analog channels share a common field ground. Multiple separated grounding points will create ground loops and measurement drift.
QA & Testing SOP (Transparency Building)
- Incoming Inspection: Verify part marking and -EA revision suffix. Inspect backplane gold pins for bending/corrosion; check module housing integrity.
- Live Testing: Mount onto validated RX3i baseplate. Inject precision voltage/current signals for all channels, verify conversion accuracy, test open-circuit diagnostic alarms and all filter settings, run continuous 24-hour acquisition stability test.
- Electrical Testing: Monitor backplane 3.3V/5V rail stability. Insulation resistance ≥10MΩ between field circuits and chassis protective ground.
- Firmware Record: Document hardware revision; photograph terminal wiring layout before disassembly.
- Final QC & Packaging: Place unit inside anti-static shielding. Attach dated QC test tag confirming channel measurement validation prior to shipment.
Installation Pitfalls & Guide
❗ Hot Swap Precondition: Supports hot swap only on hot-swap rated RX3i universal backplanes. Non-hot-swap racks require full rack power shutdown before module replacement. ❗ Uniform Wiring Mode Rule: The entire module must be set to all single-ended OR all differential; mixed wiring topology on the same module produces invalid readings. ❗ Ground Loop Risk Warning: Non-isolated design. All transmitter grounds should be referenced to one single ground point to avoid signal drift. ❗ Terminal Block Separate Item: Module does not include terminal block; order IC694TBB032 or IC694TBS032 separately. ❗ Filter Tuning Guidance: Low filter frequencies (8Hz) provide best power-line noise rejection but slow response speed. ❗ ESD Risk: Static discharge damages ADC front-end circuits; symptoms include unstable channel readings and offset drift.
Replacement Guide
- Pre-install: Lockout-tagout rack power; back up I/O hardware configuration. Photograph analog field wiring and terminal arrangement. Record configured filter settings and channel ranges.
- Removal: Disconnect terminal block field wiring, unlatch module and slide straight out without twisting backplane pins.
- Instew into original slot, attach terminal block and replicate all field wiring connections.
- Power-on Test: Restore rack power, download saved configuration, verify all channel readings and confirm open-circuit diagnostic function operates correctly.
FAQ
es support hot swapping? A: Yes, on hot-swap certified RX3i universal backplanes. Non-hot-swap racks require full rack power shutdown.
Q: What does the -EA suffix mean? A: -EA denotes a specific PCB hardware revision. Core analog functionality identical to other variants, mechanically plug-compatible. Always perform full channel verification after replacement.
Q: What is the diffeen and IC695ALG626? A:
- : Non-isolated, high density, lower cost
- IC695ALG626: Group-channel isolated analog input, suppresses ground loops for multi-ground field wiring They are not directly interchangeable without reviewing field grounding design.
Q: Can I mix voltage and current signal ranges on the same module? A: Yes, each channel can be independently configured for voltage or current ranges via PME software.
Q: Does this module support HART transmitters? A: No native HART pass-through capability.
Q: Can this module be installed on serial expansion racks via IC695LRE001? A: Yes, compatible with RX3i serial expansion rack architecture.
Q: Will I/O configuration automatically work on a replacement module? A: Channel configuration resides in the CPU project. After replacement, verify wiring mode (single-ended/differential), filter parameters and channel range settings.