Product Core Brief
- Model: CC-PAIN01
- Brand: Honeywell
- Series: Experion PKS C300
- Core Function: Acquires high-level analog current signals from two-wire transmitters for C300 controllers.
- Product Type: HLAI I/O Module
- Key Specs: 16 Channels | 4-20 mA | 16-Bit ADC
- Condition: New Original (New Surplus)
Product Introduction
HONEYWELL CC- acts as a high-level analog input module for C300 controllers. This unit accepts 4-20 mA current inputs from standard two-wire or self-powered transmitters.
Unlike HART-enabled variants, this module focuses on fast loop scanning and basic signal conditioning. Hardware accuracy sits at ±0.075% of full-scale at 23.5 °C. Verify with OEM datasheet for exact temperature drift coefficients.

Honeywell CC-PAIN01
Key Technical Specifications
| Parameter | Value |
|---|---|
| Channel Count | 16 Single-Ended |
| Input Type | 4-20 mA Current |
| ADC Resolution | 16 Bits |
| Input Scan Rate | 50 ms |
| Hardware Accuracy | ±0.075% Full-Scale |
| Max Normal Mode Input | ±30 V |
| Crosstalk | -60 dB |
| Controller Family | C300 |
Quality Control Process (Engineer’s Perspective)
- Incoming Verification: We trace source serial numbers against factory records. Visual inspection checks for pin corrosion or PCB scratches.
- Live Functional Test: Power-on self-check runs first. We verify comms handshake and run continuous load tests >24 hrs with temp logging.
- Electrical Parameter Test: Insulation resistance gets tested at 500 V Megger (>10 MΩ required). Ground continuity is mandatory.
- Firmware Verification: Read and record firmware version immediately. Photograph DIP switch and jumper settings before racking.
- Final QC & Packaging: Seal in anti-static bag. Apply QC Passed label with test date and engineer initials.
Replacement Pitfall Guide
❗ Firmware Mismatch: New module firmware may conflict with older C300 controllers. Always check version compatibility before racking.
❗ DIP Switch / Jumper Misconfiguration: Factory defaults rarely match field settings. Verify bus termination resistor placement on the third terminal block.
❗ Terminal / Cable Incompatibility: Pin definitions change between revisions. Check shield grounding at the CC-TAIN01 terminal board.
❗ Power Supply Mismatch: Calculate total rack power draw. Maintain 20% headroom on your 24 V DC supply to prevent brownouts.
❗ ESD Damage: Use anti-static mat and wrist strap. Dry environments increase failure risk during handling.
Keep these in mind and you’ll cut 90% of rework time.

Honeywell CC-PAIN01
Compatibility Matrix & Benchmarks
- CC- → CC-PAIH01 : Needs Adaptation — Adds HART protocol support
- CC- → CC-TAIN01 : Direct — IOTA base unit, not a module replacement
- CC- → CC-PAIX01 : Incompatible — Different signal type and channel count
Benchmarks:
- Scan cycle: 50 ms (continuous loop, 16 I/O points)
- Comms throughput: N/A (No HART protocol on this variant)
Need me to pull up the pinout and wiring diagram for CC-? Let me know.